| 2004-01-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR: A)SLIDER WINDOW. |
| | B)GLASS BLOCK. C)ROOF TILE. D)SINGLE |
| | HUNG WINDOWS. E)ENTRY DOOR WITH SIDE- |
| | LITE ASSEMBLY. F)SLIDING GLASS DOORS. |
| | G)WINDOW MULLIONS. H)TRUSS CONNECTORS. |
| | 3-ARCHITECT TO HAVE ALL HIS INFORMATION |
| | AND REQUIREMENTS OF CHAPTER 481 FL. |
| | 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY |
| | NEED SPECIFIC UL LISTED ASSEMBLY AND |
| | REVISE DETAIL TO INCLUDE ALL REQUIRED |
| | COMPONENTS ON LISTED ASSEMBLY.SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL |
| | E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| | REVISE AS REQUIRED. |
| | 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC REGARD'G THE STEEL STRESS |
| | B)SPECIFY SIZES FOR USP RT CONNECTORS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | FASTENER AS REQ'D BY SEC. 104.2.1.1 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH |
| | 28-3 CONNECTOR TAKEN FROM?. UNABLE TO |
| | FIND ON USP 2003 CATALOGUE. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | B)MISSING ONE CONNECTOR FOR REAR PORCH |
| | GIRDER TRUSS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | C)CLARIFY WHY THE DESIGN PRESSURES ARE |
| | THE SAME FOR DIFFERENT OPENING SIZE & |
| | LOCATION. SEC. 104.2.1.2 CITY AMENDM. |
| | D)WINDOWS SHOWN ON REAR ELEVATION DON'T |
| | MATCH WINDOW SCHEDULE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |