| Plan Review Notes For Permit 03121472 |
| Permit Number |
03121472 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS | | | ROOF TILE, MULLIONS, GLASS BLOCK AND | | | STRUCTURAL CONNECTORS. | | | 2-REVISE DETAIL E/4. FASTENER SPECIFIED | | | DOESN'T PROVIDE 2" MIN. EMBEDMENT. | | | 3-PROVIDE ENGINEERING FOR TRUSS ANCHOR | | | FASTENERS OTHER THAN THOSE TESTED AND | | | PUBLISHED BY USP TO COMPLY WITH SEC. | | | 1609.4.3 FBC 2001 REGARDING STEEL | | | STRESS. | | | 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 | | | AND 8 TAKEN FROM FOR ROOF TILE FASTE- | | | NING. SEE ASCE 7-98 AND FBC 2001. | | | 5-SHEET #7: A)REVISE DESIGN PRESSURES AT | | | EXTERIOR OPENINGS. SEE TABLES 1606.2B | | | AND 1606.2E FBC 2001. | | | B)DESIGN PRESSURES SHOWN DON'T MATCH | | | THOSE SHOWN ON SHEET 3. | | | C)REVISE ALL REAR PORCH FLOOR PLAN AND | | | ROOF PLAN NOTES REGARDING WOOD BEAM. | | | IT WAS CHANGED TO CONCRETE BEAM. | | | D)WINDOWS SHOWN ON EXTERIOR ELEVATION | | | DON'T MATCH WINDOW SCHEDULE. |
|