| 2004-01-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-STORM SHUTTERS: A)REVISE KEY PLAN AND |
| | INSTALLATION SCHEDULE. NEED EMERGENCY |
| | EGRESS THAT COMPLIES WITH SECTION |
| | 1005.4.5 FBC 2001. |
| | B)CLEARLY MARK ON SHUTTERS DWGS SPECIFIC |
| | ANCHOR & SPACING TO BE USED ACCORDING |
| | TO MOUNTING CONDITIONS, EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE AND THE |
| | STRUCTURE TO BE ATTACHED TO (MASONRY |
| | OR CONCRETE). SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR: |
| | A)HORIZONTAL SLIDER WINDOW: NEED THE |
| | APPROVED DRAWINGS. |
| | B)GLASS BLOCK. |
| | C)ROOF TILE (FBC APPROVAL IS PENDING). |
| | D)SINGLE HUNG WINDOWS. |
| | E)ENTRY DOOR WITH SIDELITE ASSEMBLY. |
| | F)SLIDING GLASS DOORS. |
| | G)WINDOW MULLIONS. |
| | |
| | 4-ARCHITECT TO HAVE ALL HIS INFORMATION |
| | ON TITLE BLOCK AS REQUIRED BY CHAPTER |
| | 481 FL STATUTES. SEE FAC SECTION |
| | 61G1-16.004. |
| | **NOTE: THIS COMMENT HAVE BEEN ADDRESSED |
| | BEFORE SEVERAL TIMES AND STILL IS |
| | NOT DONE. |
| | 5- 1 HR. FIRE RATED GLASS BLOCK ASSEMBLY |
| | NEED SPECIFIC UL LISTED ASSEMBLY AND |
| | REVISE DETAIL TO MATCH SUCH ASSEMBLY. |
| | SPECIFY ALL COMPONENTS THAT MAKE THE |
| | ONE HR. FIRE RATED ASSEMBLY.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL |
| | E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| | CHECK SIZE OF FASTENER. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC 2001. |
| | B)SPECIFY USP RT SIZES TO VERIFY VALUE |
| | SPECIFIED ON CATALOGUE. |
| | NOTE: PROVIDE ENGINEERING CALCS FOR |
| | VALUES OTHER THAN THOSE PUBLISHED ON |
| | CATALOGUE. SECTION 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-ENGINEER TO SPECIFY ROOF TILE FASTENER |
| | AS REQ'D BY SEC. 104.2.1.1OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 9-REVISE WINDOW/DOOR BUCK DETAIL. SEE |
| | SEC. 1707.4.4.2 FBC 2001 FOR PROPER |
| | BUCK INSTALLATION. |
| | 10-CLARIFY WHERE IS CONNECTOR USP |
| | EHUH 28-3 TAKEN FROM?. INABLE TO FIND |
| | ON USP CATALOGUE. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 11-SHEET #7:A)MISSING CONNECTOR AT ONE |
| | END OF GIRDER TRUSS AT PORCH. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | B)REAR ELEVATION: CLARIFY WHY DESIGN |
| | PRESSURES ARE THE SAME, EVEN FOR OPG'S |
| | BIGGER THAN OTHERS. REVISE AS REQ'D. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096. |
| 2003-12-24 00:00:00 | ENTERED IN ERROR |