| 2004-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-SOME DRAWINGS ARE MISSING INFORMATION |
| | REQUIRED BY ARCHITECT TO BE INCLUDED |
| | IN ALL PLANS. CHAPTER 481 FL STATUTES. |
| | NAME OF ARCHITECT AND DATE OF SEALING. |
| | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR WINDOWS, DOORS, |
| | GLASS BLOCK, ROOF TILE, MULLIONS AND |
| | STRUCTURAL CONNECTORS. |
| | 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK FASTENER SIZE. |
| | 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| | FOR TYPE/NUMBER OF FASTENERS OTHER |
| | THAN THOSE TESTED AND PUBLISHED BY USP |
| | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| | 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001 AND SECTION |
| | 1606.3 FBC 2001. |
| | 6-REVISE WINDOW BUCK DTAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR |
| | OPENING DESIGN PRESSURES ACCORDING TO |
| | SIZE AND LOCATION. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)PROVIDE ENGINEERING CALCS FOR SYMPSON |
| | EG7 CONNECTOR FASTENERS, SINCE THEY'RE |
| | DIFFEENT THAN THOSE TESTED & PUBLISHED |
| | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |