| 2004-01-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| | MENTS OF CHAPTER 481 FLORIDA STATUTES |
| | WHEN SUBMITTING DWGS FOR PUBLIC RECORD |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR: ALL DOORS/WINDOW |
| | TYPE, GLASS BLOCK MULLIONS, ROOF TILE |
| | AND STRUCTURAL CONNECTORS. |
| | 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY AND |
| | REVISE DETAIL TO MATCH AL COMPONENTS |
| | ON SUCH ASSEMBLY. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK FASTENER SIZE. |
| | 6-A)UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS THAT ARE AFFECTED BY SECTION |
| | 1609.4.3 FBC REGARDING STEEL STRESS. |
| | NEED ENGINEERING CALCS FOR DIFFERENT |
| | VALUES AND FASTENERS OTHER THAN THOSE |
| | PUBLISHED ON REVISED CATALOGUES. |
| | B)SPECIFY SIZE OF USP RT STRAPS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-A)DESIGN PRESSURES FOR EXTERIOR OPG'S |
| | DON'T MATCH TABLES 1606.2B & 1606.2E |
| | FBC 2001 ACCORDING TO SIZE/LOCATION. |
| | PROVIDE CALCULATIONS FOR PRESSURES |
| | THAT AREN'T CLOSE TO ABOVE TABLES. SEC |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | B)PROVIDE CALCULATIONS TO SHOW SIMPSON |
| | EG-7 CONNECTOR COMPLIANCE WITH SECTION |
| | 1609.4.3 FBC 2001 SINCE FASTENERS ARE |
| | DIFFERENT FROM THOSE ALREADY TESTED & |
| | PUBLISHED BY SIMPSON. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |