| 2004-01-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL WINDOWS AND |
| | DOORS, GLASS BLOCK, MULLIONS, ROOF |
| | TILE AND STRUCTURAL CONNECTORS. |
| | 2-REVISE DETAIL E/4. FASTENER SPECIFIED |
| | DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE ENGINEERING CALCULATIONS FOR |
| | NUMBER OF FASTENERS SPECIFIED ON TRUSS |
| | ANCHOR SCHEDULE SINCE THEY DIFFER FROM |
| | TESTED AND PUBLISHED VALUES BY USP TO |
| | COMPLY WITH SEC. 1609.4.3 FBC 2001 |
| | REGARDING THE STEEL STRESS LIMITATION. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 4-CLARIFY WHERE ARE TABLES 6 AND 8 NOTED |
| | ON DETAIL A/4 FOR ROOF TILE FASTENING |
| | TAKEN FROM?. WEE FOLLOW FBC 2001 AND |
| | ASCE 7-98 AND THEY DON'T HAVE THOSE |
| | TABLES. SEC. 104.2.1.2 CITY AMENDMENTS |
| | 5-SHEET A7: A)REVISE DESIGN PRESSURES. |
| | SEE TABLES 1606.2B AND 1606.2E FBC. |
| | B)DESIGN PRESSURES SHOWN ON THIS SHEET |
| | AND SHEET 3 DON'T MATCH. |
| | C)REVISE SPECS ON FLOOR PLAN & ROOF PLAN |
| | TO REFLECT CHANGE OF BEAM FROM WOOD TO |
| | CONCRETE BEAM. REVISE TRUSS ANCHOR AND |
| | NOTES FOR WOOD BEAM. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | D)WINDOWS SHOWN ON ELEVATION DON'T MATCH |
| | THOSE ON WINDOW SCHEDULE. REVISE. |