| 2004-01-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-STORM SHUTTERS: A)REVISE KEY PLAN AND |
| | INSTALLATION SCHEDULE. NEED EMERGENCY |
| | EGRESS THAT COMPLIES WITH SECTION |
| | 1005.4.5 FBC 2001. MAKE SURE KEY PLAN |
| | MATCHES FLOOR PLAN SUBMITTED. |
| | B)CLEARLY INDICATE ANCHOR TYPE & SPACING |
| | TO BE USED ACCORDING TO EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE, DESIGN |
| | PRESSURES & STRUCTURE TO BE ATTACHED |
| | TO (MASONRY OR CONCRETE). |
| | 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR: |
| | A)HORIZONTAL SLIDER WINDOW: NEED THE |
| | APPROVED DRAWINGS. |
| | B)GLASS BLOCK. |
| | C)ROOF TILE(FBC APPROVAL IS PENDING) |
| | D)SINGLE HUNG WINDOWS. |
| | E)ENTRY DOOR WITH SIDELITE ASSEMBLY. |
| | F)SLIDING GLASS DOORS. |
| | G)WINDOW MULLIONS. |
| | H)TRUSS CONNECTORS. |
| | |
| | 4-ARCHITECT TO HAVE ALL HIS INFORMATION |
| | ON TITLE BLOCK AS REQUIRED BY CHAAPTER |
| | 481 FLORIDA STATUTES. SEE FAC SECTION |
| | 61G1-16004. |
| | **THIS COMMENT HAS BEEN ADDRESSED ON |
| | PREVIOUS REVIEWS. |
| | 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY |
| | NEED SPECIFIC UL LISTED ASSEMBLY AND |
| | REVISE DETAIL TO MATCH SUCH ASSEMBLY. |
| | SPECIFY ALL COMPONENTS REQUIRED TO |
| | MEET THE ONE HR FIRE RATED ASSEMBLY. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL |
| | E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| | CHECK SIZE OF FASTENER. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC 2001. |
| | B)SPECIFY USP RT SIZES TO VERIFY VALUE |
| | SPECIFIED ON CATALOGUE. |
| | 8-ENGINEER TO SPECIFY ROOF TILE FASTENER |
| | AS REQ'D BY SEC. 104.2.1.1 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 9-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 10-SHEET #7: A)CLARIFY WHERE IS USP |
| | EHUH 28-3 TAKEN FROM?. UNABLE TO FIND |
| | IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)MISSING SPECIFICATIONS FOR CONNECTOR |
| | AT ONE END OF GIRDER TRUSS AT REAR |
| | PORCH. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | C)REAR ELEVATION: CLARIFY CALCULATED |
| | DESIGN PRESSURES. WHY SAME PRESSURES |
| | FOR DIFFERENT SIZE/LOCATION OF OPG'S? |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | |