| Plan Review Notes For Permit 03121448 |
| Permit Number |
03121448 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-05 00:00:00 | DENIED: | | | RETURN AIR FROM THE MASTER BEDROOM IS | | | NOT SIZED PROPERLY.PER 2001 FBC(M) | | | 601.4 EXECPTION #3, ALL SUPPLY AIR INTO | | | THE MASTER SUITE SHALL BE INCLUDED FOR | | | THE PROPER SIZING OF THE RETURN AIR TO | | | THAT SPACE. PLEASE SEE ATTACHED SCHEDULE | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|