| 2004-01-26 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-SOME DRAWINGS NEED TO HAVE ALL INFO. |
| | REQUIRED BY THE ARCHITECT AS REQ'D |
| | BY CHAPTER 481 FLORIDA STATUTES. |
| | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR DOORS, WINDOWS, |
| | ROOF TILE, GLASS BLOCK, MULLIONS AND |
| | STRUCTURAL CONNECTORS. |
| | 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK FASTENER SIZE. |
| | 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| | FOR TYPE/NUMBER OF FASTENERS WHEN THEY |
| | ARE DIFFERENT THAN THOSE TESTED AND |
| | PUBLISHED ON CATALOGUE TO COMPLY WITH |
| | SEC. 1609.4.3 FBC 2001. |
| | 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 6-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.42 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR |
| | OPENINGS DESIGN PRESSURES ACCORDING |
| | TO SIZE AND LOCATION. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | B)PROVIDE ENGINEERING CALCS FOR SYMPSON |
| | EG7 FASTENERS, SINCE THEY ARE DIFFEENT |
| | FROM THOSE TESTED AND PUBLISHED TO |
| | COMPLY WITH SEC. 1609.4.3 FBC 2001. |