| 2004-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-SOME DRAWINGS ARE MISSING INFORMATION |
| | REQUIRED BY ARCHITECT TO BE INCLUDED |
| | IN ALL PLANS AS REQ'D BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | 2-PROVIDE COMLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR DOORS, WINDOWS, |
| | GLASS BLOCK, MULLIONS, ROOF TILE AND |
| | STRUCTURAL CONNECTORS. |
| | 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK FASTENER SIZE. |
| | 4-TRUSS ANCHOR SCHEUDLE: PROVIDE CALCS |
| | FOR TYPE/NUMBER OF FASTENERS OTHER |
| | THAN THOSE TESTED AND PUBLISHED BY USP |
| | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| | 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS AS REQUIRED BY SEC. |
| | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| | 6-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 7-SHEET #3: A)REVISE DESIGN PRESSURES. |
| | SEE TABLES 1606.2B AND 1606.2E FBC FOR |
| | MIN. PRESSURES ACCORDING TO SIZE AND |
| | LOCATION OF OPENING. |
| | B)PROVIDE ENGINEERING CALCS FOR SIMPSON |
| | EG7 FASTENERS,SINCE THEY ARE DIFFERENT |
| | THAN THOSE TESTED AND PUBLISHED BY USP |
| | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |