| 2004-01-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ARCHITECT TO COMPLY WITH CHAPTER 481 |
| | FLORIDA STATUTES WHEN SUBMITTING DWGS |
| | FOR PUBLIC RECORDS. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL DOORS/WINDOWS |
| | TYPE, MULLIONS, GLASS BLOCK, ROOF TILE |
| | AND ALL STRUCTURAL CONNECTORS. |
| | 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY AND |
| | REVISE DETAIL ACCORDINGLY. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK FASTENERS. |
| | 6-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS TO COMPLY WITH SEC. 1609.4.3 |
| | FBC 2001.PROVIDE ENGINEERING CALCS |
| | FOR DIFFERENT VALUES AND FASTENERS. |
| | SEE REVISE CATALOGUES. |
| | B)SPECIFY SIZE FOR RT USP STRAPS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENER. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-REVISE DESIGN PRESSURES FOR EXTERIOR |
| | OPENINGS. SEE TABLES 1606.2B AND |
| | 1606.2E FOR PRESSURES ACCORDING TO |
| | SIZE AND LOCATION. PROVIDE ENGINEERING |
| | CALCS FOR DIFFERENT VALUES. |
| | 10-PROVIDE ENGINEERING CALCS FOR SIMPSON |
| | EG-7 CONNECTOR SHOWING COMPLIANCE WITH |
| | SEC. 1609.4.3 FBC REGARDING THE STEEL |
| | STRESS SINCE FASTENERS AREN'T THE SAME |
| | AS TESTED AND PUBLISHED BY SIMPSON. |
| | |