| Date |
Text |
| 2004-01-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL WINDOW/DOOR |
| | TYPE, GLASS BLOCK, MULLIONS,ROOF TILE, |
| | STRUCTURAL CONNECTORS. |
| | 2-REVISE DETAIL E/4. FASTENER SPECIFIED |
| | DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE ENGINEERING CALCS FOR TRUSS |
| | ANCHOR FASTENERS SINCE THEY ARE |
| | DIFFERENT FROM TESTED & PUBLISHED |
| | VALUES BY USP TO COMPLY WITH SECTION |
| | 1609.4.3 FBC 2001 REGARDING THE STEEL |
| | STRESS INCREASE.SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-ROOF TILE FASTENERS ON DETAIL A/4 CALL |
| | FOR TABLES 6 AND 8. THESE TABLES ARE |
| | NOT IN FBC 2001 OR ASCE 7-98. CLARIFY. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 5-SHEET A-7: A)REVISE DESIGN PRESSURES @ |
| | EXTERIOR OPENINGS. SEE TABLES 1606.2B |
| | AND 1606.2E FBC 2001. |
| | B)DESIGN PRESWSURES SHOWN ON THIS PAGE |
| | DON'T MATCH DESIGN PRESSURES SHOWN ON |
| | SHEET 3. |
| | C)REVISE REAR PORCH FLOOR PLAN AND ROOF |
| | PLAN. BEAM WAS CHANGED TO CONCRETE BM. |
| | THERE ARE SOME NOTES THAT STILL CALL |
| | FOR GIRDER TRUSS CONNECTORS AND |
| | BUILD-UP. REVISE AS REQUIRED. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | D)WINDOWS SHOWN ON EXTERIOR ELEVATION |
| | DON'T MATCH WINDOW SCHEDULE. |