| 2004-01-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR: SLIDER WINDOWS, |
| | GLASS BLOCK, ROOF TILE, SINGLE HUNG |
| | WINDOWS, ENTRY DOOR WITH SIDELITE, |
| | SLIDING GLASS DOORS, WINDOW MULLIONS |
| | AND TRUSS CONNECTORS. |
| | 3-ARCHITECT TO PROVIDE ALL INFORMATION |
| | REQUIRED BY CHAPTER 481 FL. STATUTES. |
| | 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY AND |
| | REVISE DETAIL TO MATCH ALL COMPONENTS |
| | REQUIRED ON LISTED ASSEMBLY. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG |
| | #2 DON'T MATCH. CHECK FASTENER SIZE. |
| | 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC REGARDING STEEL STRESS. |
| | B)SPECIFY SIZE OF USP RT STRAPS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENER. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-SHEET #7: A)WHERE IS USP EHUH 28-3 |
| | CONNECTOR TAKEN FROM?. UNABLE TO FIND |
| | IN USP 2003 CATALOGUE. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | B)MISSING ONE CONNECTOR AT GIRDER TRUSS |
| | LOCATED IN REAR PORCH. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | C)WHY DESIGN PRESSURES SHOWN ON REAR |
| | ELEVATION ARE THE SAME FOR OPENINGS |
| | WITH DIFFERENT SIZE & LOCATION?. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | D)WINDOWS SHOWN ON REAR ELEVATION DON'T |
| | MATCH WINDOW SCHEDULE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |