| 2003-12-31 00:00:00 | *********** UNSAT ************* |
| | |
| | |
| | *** NOTE*** UNABLE TO DUE COMPLETE |
| | REVIEW AT THIS TIME DUE TO PLANS MISSING |
| | RISER DIAGRAM FOR SERVICE. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT COMPLETE RISER |
| | DIAGRAM. 215.5,250.50,110.9, 310.15B6 |
| | 250.66 ETC |
| | |
| | 2)NOTE: PLEASE CLARIFY MASTER BATH NOT |
| | SHOWN ON PANEL SCHEDULE? OTHER BATHS |
| | SHOWN AND PER 210.52D,210.11C3 OTHER |
| | BATHS MAY NOT BE ON EITHER OF THESE. |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. PER 210.8A6 |
| | |
| | 4)NOTE: PLEASE SEE 210.52C1 FOR RECEPT |
| | SPACING ALONG KITCHEN COUNTERSPACE. |
| | MISSING A FEW. |
| | |
| | 5)NOTE: PLEASE SHOW /NOTE ALL OUTSIDE/ |
| | GARAGE RECEPTS AS GFI. 210.8 |
| | |
| | 6)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | LIVING RM PER 210.52/ 2' WALL. |
| | |
| | 7)NOTE: PLEASE SEE THAT NOTE ON PLAN |
| | MENTIONS SD TO BE 3' FROM RETURN. |
| | PLEASE SEE NFPA-72, STATES TO BE 3' FROM |
| | SUPPLY GRILLES. NFPA DOES NOT STATE R/A |
| | TYP PER MANF SPECS AND CITY OF WPB SD'S |
| | ARE TO BE 5' FROM RETURN AIR. |
| | |
| | 8)NOTE: PLEASE SEE THAT PLANS ONLY |
| | SHOW ONEA/C CONDENSER UNIT? |
| | PLEASE SHOW ADDITIONAL UNIT AS SHOWN |
| | ON PANEL SCHEDULE. |
| | PLEASE ALSO SHOW/CLARIFY LOCATION OF |
| | AHU #2? ALSO 210.70/210.63 LOCATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |