| 2004-02-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PROVIDE IMPACT FEES PAID RECEIPT. |
| | 2-SURVEY SAYS FLOOD ZONE A8. FLOOD ZONE |
| | WAS CHANGED TO B PER LETTER OF MAP |
| | REVISION DATED DEC 3 1985. REVISE INFO |
| | ON SURVEY AS REQUIRED. |
| | 3-AS OF OCT. 1ST 2003 NEED TO PROVIDE |
| | FLORIDA OR LOCAL PRODUCT APPROVAL FOR |
| | ALL TYPES OF DOORS, WINDOWS, MULLIONS |
| | (AS SHOWN ON PLANS), ROOF TILE AND ALL |
| | STRUCTURAL CONNECTORS AS REQUIRED BY |
| | RULE 9B-72. |
| | 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 5-DRAWING #3 IS MISSING ENGINEER'S LOGO |
| | AND SEAL, SIGNATURE AND DATE. |
| | 6-SPECIFY ROOF TILE FASTENERS. SEE SEC. |
| | 1606.3 FBC 2001 AND SECTION 104.2.1.1 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 7-PROVIDE COMPLETE SECTION/DETAIL THRU |
| | MASONRY COLUMNS @ ENTRY AND REAR PORCH |
| | SHOWING FOOTING LOCATION IN RELATION |
| | TO FINISH GRADE. ALSO, NEED TO SHOW |
| | COMPLETE SPECS FOR VERTICAL REINFORCE- |
| | MENT. PROVIDE CALCULATIONS TO SHOW HOW |
| | THESE COLUMNS (FRONT AND REAR WILL |
| | PROVIDE SUPPORT FOR UPLIFT LOADS). |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 8-SPECIFY SIZE OF ATTIC ACCESS. SEE SEC. |
| | 2309.6 FBC 2001. |
| | 9-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| | HANGING OF AHU. SPECIFY ALL FASTENERS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 10-SHEET #5B: A)SPECIFY TRUSS CONNECTORS |
| | FOR ALL TRUSSES. |
| | B)PROVIDE DETAILS FOR INSTALLATION OF # |
| | OF ANCHORS AT UNION OF TRUSSES TO COLS |
| | AS SPECIFIED ON TRUSS ANCHOR SCHEDULE. |
| | SEE ROOF FRAMING PLAN FOR COMMENTS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 11-REVISE DETAIL 28/4S2. SEE ZONE 3 ON |
| | FIGURE 1606.2(C) FBC 2001. |
| | 12-PROVIDE DETAIL/SPECS FOR INSTALLATION |
| | OF CEILING AT ENTRY AND REAR PORCH. |
| | SEE ASTM C-926 & ASTM C-1063. SPECIFY |
| | STUCCO THICKNESS AND FASTENER SIZE AND |
| | SPACING. SEC. 2504.2 FBC 2001. |
| | 13-SHOW ONLY DETAILS THAT APPLY TO THIS |
| | PROJECT. |
| | 14-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 15-GARAGE BUCK DETAIL 3/4S1 AND DETAIL |
| | 3/4S4 DON'T MATCH. CHECK SIZE AND MIN. |
| | NUMBER OF ANCHORS. ALSO,SPECIFY ANCHOR |
| | SPACING AT THE END OF BUCK AND SPECIFY |
| | SIZE OF WASHERS. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 16-DWG #4S4: CLARIFY BUTT GLAZING NOTE: |
| | IS THERE ANY BUTT GLAZING IN MORNING |
| | AREA OR THERE ARE FIXED WINDOWS WITH |
| | STOREFRONT SYSTEM? EITHER WAY NEED |
| | PRODUCT APPROVAL. SEE SEC. 2406.2 FBC. |
| | 17-PROVIDE AREA TABULATIONS INCLUDING |
| | A/C AREAS, PORCHES, GARAGE ETC. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |