| 2004-02-09 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2} PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| | PANELS SO THAT CODE COMPLIANCE OF |
| | CIRCUITS CAN BE DETERMINED. |
| | |
| | 3} PLEASE SHOW PANEL "A" LOCATION ON |
| | PLAN. |
| | |
| | 4} PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5.COUNTERTOP SPACING |
| | IS INCORRECT. |
| | |
| | 5} THE BATHROOM OFF THE KITCHEN IS |
| | REQUIRED TO HAVE A GFI RECEPTACLE PER |
| | 210.52(D) & COMLPY WITH 210.11(C)(3). |
| | |
| | 6} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |
| | |
| | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW |
| | NOTES. PLEASE CORRELATE PLANS/PAPERWORK |
| | FOR COTTAGES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |