| 2004-01-08 00:00:00 | |
| | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | ON THE PLAN FOR CODE COMPLIANCE AS |
| | NOTED. |
| | |
| | 1} THE RISER DIAGRAM SHOWS THE 200 AMP |
| | PANEL AS NEW AND LISTS IT AS EXISTING |
| | ON THE NOTE.IT IS AGAIN LISTED AS "NEW" |
| | AT THE SITE LOCATION.PLEASE CORRELATE. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3} THE PANEL SCEDULE APPEARS TO HAVE THE |
| | BREAKER AND BREAKER AMPSINCORRECT FOR |
| | THEIR EQUIPMENT SERVED. |
| | |
| | 4} THE #6 WIRE SHOWN ON A 100 AMP |
| | BREAKER (COND UNITS) DOES NOT COMPLY |
| | WITH 310.16. |
| | |
| | 5} THE NEUTRAL FEEDING PANEL "B" IS |
| | SHOWN AS #3/0,PLEASE VERIFY. |
| | |
| | 6} PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| | PANELS SO THAT CODE COMPLIANCE OF |
| | CIRCUITS AND OCP CAN BE DETERMINED. |
| | |
| | 7} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210.52C 1,2,3,4,AND 5. |
| | |
| | 8} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 9} PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 10} PLEASE ADD THE SMOKE DETECTOR ON THE |
| | FIRST FLOOR AT THE STAIR TO COMPLY WITH |
| | 905.2.2 FBC AND NFPA-72 |
| | |
| | 11} INCREASE THE BUILDING PERMIT |
| | VALUATION PER 104.6.5 CWPB AMMENDMENTS |
| | TO THE FBC, ATTACHED. |
| | |
| | 12} ONLY ONE SET OF DRAWINGS ARE SEALED |
| | BY THE ENG. ON SHEET E-1.ALSO NOTE THAT |
| | SHEETS A-1 & A-2 ARE NOT SIGNED AND |
| | SEALED BY THE ENGINEER OF RECORD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |