| 2004-06-11 00:00:00 | *********** UNSAT ************* |
| | |
| | PLANS WENT OUT W/OUT ALL REVIEWS BEING |
| | DONE. PLANS ARE BEING SENTTO |
| | RESIDENTIAL RACK FOR OTHER TRADE REVIEWS |
| | |
| | 1)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. ONE SET HAS REDLINED AREAS. |
| | |
| | 2)NOTE: PLEASE SEE 210.52C-3 FOR PENIN- |
| | -SULAR RECEPT. |
| | |
| | 3)NOTE: PLEASE SEE CORNERS OF HOUSE |
| | SHOW SCONCES AS SHOWN ON FRONT OF GARAGE |
| | ? PLEASE SEE PLANS DO NOT INDICATE TYPE |
| | FIXTURE AND/OR CONTROL FOR THESE. |
| | |
| | 4)NOTE: PLEASE SEE PANEL SHOWS A MCB, |
| | AND A MAIN DISCONNECT ON OUTSIDE OF |
| | HOUSE. THIS IS PERMITTED, HOWEVER IT IS |
| | NOT REQUIRED. IF SHOWN THIS WAY ON PLANS |
| | THEN THEY BOTH WILL BE REQUIRED TO BE |
| | INSTALLED. THIS IS ONLY A NOTE. |
| | |
| | 5)NOTE: PLEAS VERIFY HEAT/ KW FOR AHU. |
| | MECH PLANS DO NOT INDICATE HEAT STRIP |
| | SIZE? |
| | THIS IS ALSO ONLY A NOTE. IF HEAT IS |
| | 10KW, PLEASE ADJUST OCP ON PANEL SCHED- |
| | -ULE AND LOAD CALCS. 424.3B |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |