| Plan Review Notes For Permit 03121403 |
| Permit Number |
03121403 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-23 00:00:00 | DENIED | | | | | | 1) SUBMIT A COPY OF THE RECORDED UNITY | | | OF TITLE FOR THE TWO LOTS. | | | | | | 2) FBC* 1804.2.2AREA OF QUESTIONABLE | | | SOIL.SUBMIT A GEOTECHNICAL REPORT | | | TO VERIFY THE SAFE BEARING CAPACITY OF | | | THE SOIL. THE REPORT SUBMITTED DOES NOT | | | MEET THE REQUIREMENTS OF FBC 1804.2.2. | | | THE REPORT IS ALSO REQUIRED TO BE SIGNED | | | AND SEALED BY THE SOIL ENGINEER. | | | | | | 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE | | | 5/8" J-BOLT FOR THE SIMPSON MGT TRUSS | | | ANCHOR. | | | | | | 4)FBC 1005.4.5 (GLITCH AMENDMENTS | | | JULY 1, 2003) REQUIRES AT LEAST ONE | | | MEANS OF ESCAPE FROM A DWELLING WHEN | | | SHUTTERED FOR IMPACT PROTECTION. THE | | | MEANS OF ESCAPE SHALL BE WITHIN THE | | | FIRST FLOOR OF THE DWELLING AND CAN NOT | | | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY | | | PART OF THE DWELLING SHALL HAVE ACCESS | | | TO IT WITHOUT HAVING TO PASS THROUGH A | | | LOCKABLE DOOR NOT UNDER THEIR CONTROL. | | | INDICATE HOW COMPLIANCE WILL BE | | | ACHIEVED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|