| Plan Review Notes For Permit 03121403 |
| Permit Number |
03121403 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | PLANS TAKEN BY ZONING, 1/2/04 | | 2003-12-31 00:00:00 | ************** UNSAT *************** | | | | | | ********** NOTE ******* | | | UNABLE TO COMPLETE PLAN REVIEW AT THIS | | | TIME, PLANS ARE MISSING RISER DIAGRAM | | | ETC. | | | | | | 1)NOTE: PLEASE CORRELATE PLANS, 200A AND | | | 250A IS SHOWN. | | | | | | 2)NOTE: PLEASE SHOW COMPLETE RISER DIA- | | | -GRAM, SEC'S, AWG, OCP, GROUNDING ELEC-- | | | TRODE SYSTEM ETC. 110.9, 250.50, 310.15 | | | B6 ETC. | | | | | | 3)NOTE: PLEASE SEE 210.52 | | | | | | 4)NOTE: PLEASE SEE 210.52D AND 210.11C3 | | | FOR BATH CIRCUIT(S). SHOWS BATHS ALL ON | | | ONE. | | | | | | 5)NOTE: PLEASE SEE PLANS NOTE , PER | | | PALM BEACH COUNTY, PLEASE ADJUST TO | | | CITY OF WPB. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|