| 2004-06-25 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A COPY OF THE PAID RECEIPT FOR |
| | THE COUNTY IMPACT FEES. |
| | |
| | 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4)ON SHEET 3 STRUCTURAL NOTE 6 SPECIFIES |
| | THAT REINFORCING STEEL BE LAPPED 48 BAR |
| | DIAMETERS. THE FILLED CELL DETAIL ON |
| | SHEET 1 AND COLUMN NOTE 1 ON 3 SPECIFY |
| | SPECIFY 30 BAR DIAMETERS. PLEASE CORRECT |
| | |
| | 5) THE UPLIFTS FOR THE 2 MEMBER GIRDER |
| | ARE 2852PSF AND 2808PSF EXCEED THE |
| | UPLIFT CAPACITY OF 1215# SPECIFIED FOR |
| | THE HUS 26-2 IN DETAIL A ON SHEET 4. |
| | |
| | 6)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | PRODUCT APPROVALS FOR THE FOLLOWING: |
| | - STRUCTURAL MULLIONS |
| | - OUTSWING GLAZED DOOR (FL PRODUCT |
| | APPROVAL DOES NOT MATCH NOA SUBMITTED) |
| | - OVERHEAD GARAGE DOOR (FL# IS NOT |
| | CORRECT, PARTS OF REPORT SUBMITTED ARE |
| | ILLEGIBLE) |
| | |
| | IF YOU HAVE QUESTIONS CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |