| Plan Review Notes For Permit 03121401 |
| Permit Number |
03121401 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-09 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE PANEL 'CW' IS STILL | | | NOT SHOWN ON RISER DIAGRAM. | | | PLEASE SEE PANEL "CW" IS SHOWN AS HAVING | | | A 225A MCB NOTED AS BEING MOUNTED ON | | | OUTSIDE OF BLDG. PANEL IS SHOWN HAVING | | | A 116A LOAD.THE OCP FEEDING 'CW' PANEL | | | FROM MDP IS SHOWN AS 100A? PLEASE | | | CORRELATE. | | | | | | 2)NOTE: PLEASE HAVE PLANS SIGNED WITH A | | | COMPLETE 'SIGNATURE" . INITIALS ARE NOT | | | ACCEPTABLE TO FS / FBPE'S. | | | FS 471.025 | | | | | | 3)NOTE: PLEASE CORRELATE LOAD ON LOAD | | | SUMMARY WITH PANELS. | | | | | | ** NEW NOTE** | | | 4)NOTE: PLEASE SEE LOAD SHOWN FOR PANEL | | | "D" IS SHOWN AT 71A'S, PANEL "A" SHOWS | | | A 3P 60 FEEDING PANEL "D". | | | PLEASE CORRELATE. | | | | | | 5)NOTE: PLEASE VERIFY ANY EQUIPMENT | | | GROUNDING CONDUCTORS MISSING PER 250.110 | | | , SIZE PER 250.122. PANEL CW, | | | | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|