Plan Review Notes
Plan Review Notes For Permit 03121401
Permit Number 03121401
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT U-1 GREASE INTECEPTOR AND OIL
 INTECEPTOR SHALL BE SIZED BY RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE PER
 WASTE ORDINANCE #2938-96. CONTACT HIM AT
 (561) 837-4074.
 2) SHT A-1 WOMEN'S AND MEN'S TOILET
 ROOMS ARE NOT LARGE ENOUGH. MINIMUM 5'3"
 WIDE ROOM REQUIRED. SEC. 405.3.1 AND
 FIGURE 28 IN CHAPTER 11.
 3) SHT A-7 CALLS FOR 3 HAND SINKS, (#10)
 AND ONLY ONE SHOWN. PLEASE CLAIRFY.
 SEC 104.2.1
 4) SHT P-1 SANITARY SEWER ISOMETRIC,
 SAFE WASTES ARE NOT APPROVED. INDIRECT
 WASTE SHALL DRAIN INTO A FLOOR SINK OR
 A HUB DRAIN. SEC 802.3 OR 802.3.2.
 5) SHT P-1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 6) L-2 UNABLE TO LOCATE RAIN BIRD TIME
 CONTROLLER AND TORO RAIN SENSOR SWITCH.
 PLEASE INDICATE LOCATION ON PLANS. SEC.
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692