| Plan Review Notes For Permit 03121401 |
| Permit Number |
03121401 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT U-1 GREASE INTECEPTOR AND OIL | | | INTECEPTOR SHALL BE SIZED BY RODNEY | | | COMPO, ENVIRONMENTAL COMPLIANCE PER | | | WASTE ORDINANCE #2938-96. CONTACT HIM AT | | | (561) 837-4074. | | | 2) SHT A-1 WOMEN'S AND MEN'S TOILET | | | ROOMS ARE NOT LARGE ENOUGH. MINIMUM 5'3" | | | WIDE ROOM REQUIRED. SEC. 405.3.1 AND | | | FIGURE 28 IN CHAPTER 11. | | | 3) SHT A-7 CALLS FOR 3 HAND SINKS, (#10) | | | AND ONLY ONE SHOWN. PLEASE CLAIRFY. | | | SEC 104.2.1 | | | 4) SHT P-1 SANITARY SEWER ISOMETRIC, | | | SAFE WASTES ARE NOT APPROVED. INDIRECT | | | WASTE SHALL DRAIN INTO A FLOOR SINK OR | | | A HUB DRAIN. SEC 802.3 OR 802.3.2. | | | 5) SHT P-1 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. | | | 6) L-2 UNABLE TO LOCATE RAIN BIRD TIME | | | CONTROLLER AND TORO RAIN SENSOR SWITCH. | | | PLEASE INDICATE LOCATION ON PLANS. SEC. | | | 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|