| 2004-01-23 00:00:00 | DENIED: | | | 1.PLANS FOR THE UNDERGROUND FUEL TANKS | | | TO BE SUBMITTED TO THE PALM BEACH COUNTY | | | D.E.R.M. FOR APPROVAL. SUBMIT PLANS | | | AT 3323 BELVEDERE RD BUILDING #502, CHIP | | | GREENE. | | | | | | PLEASE NOTE ADDITIONAL PERMITS REQUIRED | | | FOR THE FUEL OIL AND WALK-IN COOLERS. | | | WALK-IN COOLER PLANS SUBMITTED WITH | | | BUILDING PLANS. | | | | | | 2.STANDS FOR CONDENSING UNITS SHALL | | | COMPLY WITH 2001 FBC 1511.7.SEE THE | | | ATTACHED SCHEDULE FOR HEIGHT REQUIREMENT | | | FOR STANDS. | | | | | | 3.AUXILIARY DRAIN LINE SHALL TERMINATE | | | AT A CONSPICUOUS POINT TO SERVE AS AN | | | ALARM.PLEASE REVISE PLANS TO HAVE | | | AUXILIARY DRAIN LINE TERMINTE TO COMPLY | | | WITH 2001 FBC(M) 307.1.3. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS REQUIRED PER | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|