2004-01-23 00:00:00DENIED:
 1.PLANS FOR THE UNDERGROUND FUEL TANKS
 TO BE SUBMITTED TO THE PALM BEACH COUNTY
 D.E.R.M. FOR APPROVAL. SUBMIT PLANS
 AT 3323 BELVEDERE RD BUILDING #502, CHIP
 GREENE.
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR THE FUEL OIL AND WALK-IN COOLERS.
 WALK-IN COOLER PLANS SUBMITTED WITH
 BUILDING PLANS.
  
 2.STANDS FOR CONDENSING UNITS SHALL
 COMPLY WITH 2001 FBC 1511.7.SEE THE
 ATTACHED SCHEDULE FOR HEIGHT REQUIREMENT
 FOR STANDS.
  
 3.AUXILIARY DRAIN LINE SHALL TERMINATE
 AT A CONSPICUOUS POINT TO SERVE AS AN
 ALARM.PLEASE REVISE PLANS TO HAVE
 AUXILIARY DRAIN LINE TERMINTE TO COMPLY
 WITH 2001 FBC(M) 307.1.3.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED PER
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.