| 2004-01-09 00:00:00 | 1) ALL RENOVATION, CONSTRUCTION, AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) FUEL TANKS AND APPURTENANT EQUIPMENT | | | PLANNED FOR AND INSTALLATION SHALL | | | COMPLY WITH NFPA 30A. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR REMOVAL AND INSTALLATION OF FUEL | | | TANKS. | | | | | | 4) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 5) BUILDING ADDRESS REQUIRED. SIX INCH | | | NUMBERS ARE REQUIRED. | | | | | | 6) PLEASE INDICATE LOCATION OF EMERGENCY | | | STOP BUTTON AND APPROPRIATE SIGNAGE | | | FOR FUEL PUMPS. | | | | | | 7) PLEASE INDICATE WARNING SIGNAGE | | | LANGUAGE AT THE FUEL PUMPS. | | | | | | 8) PLEASE INDICATE LOCATIONS OF | | | FIRE EXTINGUISHERS AT FUEL PUMPS. | | | | | | 9) PROPOSED LOCATION MAY BE LOCATED | | | IN THE CITY FIRE LIMITS. CERTAIN | | | RESTRICTIONS MAY APPLY. PLEASE SEE | | | APPENDIX TO THE FLORIDA BUILDING CODE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|