| Plan Review Notes For Permit 03121401 |
| Permit Number |
03121401 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-07 00:00:00 | FAILED: | | | 1. DUMPSTER ENCLOSURE MUST HAVE A 12'-6" | | | MIN. OPENING BETWEEN THE POSTS, IF TO BE | | | PICKED UP BY THE CITY. | | | 2. ALL PARKING STALLS MUST BE PAINTED | | | WITH DOUBLE 4" WIDE PER CITY OF WPB | | | REQUIREMENT. | | | 3. PLEASE CONTACT RODNEY COMPO AT | | | 837-4051 EXT. 4074 FOR INSTALLATION AND | | | REQUIREMENT OF THE PROPOSED OIL,GREASE | | | WATER SEPARATOR AND RECLAIM WATR SYS. | | | 4. PLANS SHOW EXISTING METERS AND BACK- | | | FLOW PREVENTERS, ARE THEY TO BE REMOVED/ | | | ABANDONED? | | | 5. PLEASE SUBMIT CIVIL PLANS ONLY TO | | | PUBLIC UTILITIES AND ENGINEERING FOR | | | THEIR REVIEW ATT; MANNY GONZALEZ | | | 659-8040 EXT. 2306. | | | 6. SHEET GR-1 DRANAGE PLAN, SHOW INLET | | | CONNECTIONS AND 110 LF OF EXFILTRATION. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|