Plan Review Notes
Plan Review Notes For Permit 03121401
Permit Number 03121401
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00************* UNSAT *********
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTES, AS
 THEY WILL HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE HAVE PLANS "SIGNED " WITH
 A COMPLETE 'SIGNATURE AS REQUIRED UNDER
 FS 471.025. FAC 61G15-23.002
 THIS OFFICE HAS RECEIVED INFORMATION
 FROM FBPE'S THAT INITIALS ARE NOT
 PERMITTEDAND/OR SIGNATURE SHOULD
 CORRELATE WITH NAME AND SIGNATURE ON
 SAID LICENSE. CONTAING A MIN OF VISABLE
 FIRST AND LAST NAME. AS ON SEAL.
  
 3)NOTE: PLEASE SHOW/IDENTIFY PANELS ON
 PLANS (LOCATIONS). PLEASE SHOW PANEL
 "CW" ON PLANS.
  
 4)NOTE: PLEASE CLARIFY/SHOW CWP AS PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  