Plan Review Notes
Plan Review Notes For Permit 03121400
Permit Number 03121400
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-02 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, NOTE
 AT BOTTOM OF RISER MENTIONS,"EXISTING"
 ELECTRICAL , YET NOTE ABOVE WHAT APPEARS
 TO BE A MAIN, MENTIONS TO "PROVIDE" A
 42K RATED MAIN BREAKER???? PLEASE SEE
 THAT THIS SOUNDS LIKE A NEW MAIN IS
 BEING INSTALLED??
 IF THIS IS THE CASE, PLEASE PROVIDE
 MORE INFORMATION ON MAIN.
 215.5
  
 2)NOTE: PLEASE ALSO PROVIDE METHOD OF
 EQUIPMENT GROUNDING FROM MAIN TO 1200A
 MLO DIST PANEL.250.110,250.24,SIZE PER
 250.122.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE TOTAL LOAD SHOWN.
 PLEASE SEE THAT ALL LOADS CAN NOT BE
 DERATED AS SHOWN AT 65%. PLEASE SEE
 220.36
  
 4)NOTE; PLEASE NOTE, PANEL 'C' ON RISER
 IS SHOWN FEEDING PANEL 'KP' PLEASE SEE
 PANEL 'C' SCHEDULE, KP IS NO WHERE TO BE
 FOUND. PLEASE CLARIFY.215.5
  
 5)NOTE: PLEASE SHOW /CLARIFY ANY NEW
 OR EXISTING LIGHTING FOR AREA SHOWN.
 LS 101 5-8
  
 PLEASE SEE COMMENT FROM OTHER REVIEWERS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]