2003-12-30 00:00:00DENIED
 1.FBC 1503.4 ROOF DRAINAGE-UNLESS
 ROOFS ARE SLOPED TO DRAIN OVER ROOF
 EDGES, ROOF DRAINS SHALL BE INSTALLED AT
 EACH LOW POINT OF THE ROOF.WHERE
 REQUIRED FOR ROOF DRAINAGE, SCUPPERS
 SHALL BE PLACED LEVEL WITH THE ROOF
 SURFACE IN A WALL OR PARAPET.THE
 SCUPPER SHALL BE LOCATED AS DETERMINED
 BY THE ROOF SLOPE AND CONTRIBUTING ROOF
 AREA.
 2. FBC 1511.6.4.2 A SCUPPER SHALL BE
 SIZED IN ACCORDANCE WITH THE FBC
 3.FPC 1503.4.4DOWNSPOUTS SHALL
 DISTCHARGE AT LEAST 1 FOOT AWAY FROM
 THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENTIONS, OR
 SPLASH BLOCKS.GUTTERS WITH DOWNSPOUTS
 ARE REQUIRED ON ALL BUILDINGS WITH EAVES
 OF LESS THAN 6" HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR A ROOF
 ABOVE ANOTHER ROOF.
 4.SUBMIT CALC'S FOR PRIMARY AND
 SECONDARY ROOF DRAINS.
 5.SUBMIT SOUTH ELEVATION DRAWING
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672