Plan Review Notes
Plan Review Notes For Permit 03121378
Permit Number 03121378
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SPECIFICATION SHEETS FROM HOTEL &
 RESTURANT DIVISION SHALL BE SUBMITTED ON
 EACH SET OF PLANS.
 2) ADDITIONAL SQUARE FOOTAGE MAY REQUIRE
 ADDITIONAL PLUMBING FACILITIES. INDICATE
 EXISTING SQUARE FOOTAGE OF SPACE AND
 SHOW EXISTING TOILET FACILITIES.
 3) DRAINAGE SHALL CONNECT TO BLDG. DRAIN
 OR BRANCH LINE NOT FLOOR DRAIN AS STATED
 ON SHT A2.0
  
 REVIEW BY KEN STEVENS