Plan Review Notes
Plan Review Notes For Permit 03121368
Permit Number 03121368
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-21 00:00:001.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 3.PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 4.SUBMIT PRODUCT APPROVALS AS
 REQUIRED.
 5.SUBMIT HEADER DETAILS INCLUDING
 SIZE AND STRAPING.
 6.SUBMIT ENERGY CALCULATIONS.
 7.SHOW SOFFIT VENTING DETAIL.
 8.SHOW ATTIC ACCESS DETAIL IN
 ACCORDANCE WITH FBC 2309.7
 9.INSTALL SAFTEY GLAZING AT TUB AREAS
 IN ACCORDANCE WITH FBC SEC. 2305.2.1
 10.SPECIFY NEW AND EXISTING AREAS.
 11.1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.SHOW IN DETAIL.
 12.SHOW WINDOW AND DOOR BUCK DETAILS.
  
 ANY QUESTIONS PLEASE CALL.
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672