| Plan Review Notes For Permit 03121144 |
| Permit Number |
03121144 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-31 00:00:00 | ************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE PLANS STILL REF 19991 | | | NEC. PLEASE ADJUST ALL NOTES AND CODES | | | TO 2002 NEC. | | | | | | 2)NOTE: PLEASE SEE 210.12 OF THE 2002 | | | NEC. REQUIREMENT HAS CHANGED. | | | | | | 3)NOTE: PLEASE HAVE ENGINEER SIGN PLANS | | | WITH COMPLETE SIGNATURE. FS 471.025 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|