| 2004-02-27 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03121093 |
| | ADD: 2301 CENTREPARK WEST DR |
| | CONT: LEIGHTON MCGINN |
| | TEL: (561)722-9696 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: COMMENTS NOT ADDRESSED FROM THE |
| | 2ND REVIEW. |
| | |
| | 1) ARCHITECT INDICATES ON SHEET A-1 KEY |
| | NOTES 13 & 14 THAT NEW OPENINGS IN THE |
| | WALL ONE A SWING DOOR (13) (2ND) THE |
| | OVERHEAD GARAGE DOOR (14). |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) OVERHEAD DOOR |
| | B) SWING DOOR |
| | *************IMPORTANT*************** |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |