| Plan Review Notes For Permit 03121093 |
| Permit Number |
03121093 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SHT A-3 SHOW CLEAR FLOOR SPACE AND | | | HEIGHT FOR ACCESSIBLE URNAL PER SECTIONS | | | 11-4.18.3 & 11-4.18.2. | | | 2) SHT A-3 SHOW CLEAR FLOOR SPACE, COUN- | | | TER HEIGHT, AND EXPOSED PIPES AND SUR- | | | FACES PER SECTIONS 11-4.24.5, 11-4.24.2, | | | AND 11-4.24.6. | | | 3) SHT P6.1 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURE IN AN "EFFECTIVE RANGE", NOT | | | IT THE CEILING. PDI-WH 201 & MANUFACTURE | | | INSTALLATION INSTRUCTIONS. | | | 4) ENGINEERS SIGNATURE IS REQUIRED ON | | | THE SEAL PER 61G15-23.002(1) FAC, & FS | | | 471.025. INITIALS NOT ACCEPTABLE PER | | | FBPE'S RULING AND BLDG OFFICIAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|