| Plan Review Notes For Permit 03121093 |
| Permit Number |
03121093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE THAT PLANS ARE REQ'D | | | TO HAVE COMPLETE SIGNATURE BY THE | | | ENGINEER OF RECORD. PEER FS 471.025 AND | | | FAC 61G15-23.002. | | | ONE SET OF PLANS ARE BEING REATINED FOR | | | RECORD FOR ABOVE MENTION. | | | | | | 2)NOTE: PLEASE SHOW LOCATION OF PANEL | | | "L1A" ON PLANS. | | | | | | 3)NOTE: PLEASE SHOW ANY/ALL CONTINOUS | | | LOADS AT 125%, 215.3, 230.42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|