| Date |
Text |
| 2004-02-02 00:00:00 | DENIED |
| | |
| | 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE. |
| | |
| | 2) SUBMIT A SIGNED AND SEALED COPY OF |
| | THE SOIL TEST REPORT. |
| | |
| | 3) SHEET A0.01 LISTS THE CONSTRUCTION AS |
| | TYPE III. BASED ON FBC TABLE 600 AND THE |
| | THE PLANS THE CONSTRUCTION IS TYPE VI. |
| | |
| | 4) NOTE 22 ON A0.01 REFERS TO FBC |
| | 1816.1.7, WHICH IS FOR TERMITE BAITING |
| | SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED |
| | CONTRACT PAID IN FULL FOR FIVE YEARS |
| | FROM THE DATE OF C.O. IS REQUIRED BEFORE |
| | THE SLAB IS POURED. |
| | |
| | 5) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED AT THE ZERO LOT LINE. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND LIST- |
| | ING INFORMATION FOR ONE HOUR FIRE RATED |
| | GLASS BLOCK. |
| | |
| | 6) REVISE THE DRYWALL FASTENING NOTE ON |
| | A3.01. THE FASTENER SPACING FOR SCREWS |
| | IS NOT MORE THAN 12"OC FOR CEILINGS AND |
| | WALLS ON FRAMING 24"OC PER FBC 2504.4.1 |
| | AND GA 216. |
| | |
| | 7) REVISE DETAIL 2 ON A4.01 TO SHOW |
| | FIREBLOCKING WHERE THE WALL AND CEILING |
| | MEET. SEE FBC 2305.1. |
| | |
| | 8) REVISE THE GLASS BLOCK DETAIL 10 ON |
| | A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY. |
| | SEE UL R2556. |
| | |
| | 9) SPECIFY THE ATTIC LIVE LOADS ON S2. |
| | FBC TABLE 1604.1 REQUIRES 30PSF FOR |
| | ATTICS WITH STORAGE AND 10PSF FOR ATTICS |
| | WITHOUT STORAGE. |
| | |
| | 10) THE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS DO NOT |
| | MATCH THE PLANS. CHECK THE NUMBER AND |
| | SIZES OF OPENINGS. CHECK FOR MINIMUM |
| | PANEL LENGTH AS LISTED IN PRODUCT |
| | APPROVAL. |
| | |
| | 11) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |