| Plan Review Notes For Permit 03121040 |
| Permit Number |
03121040 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-01 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE COMMENTS FROM FIRST | | | REVIEW. | | | | | | | | | 2)NOTE: PLEASE PROVIDE ADDRESS IN TITLE | | | BLOCK/LOT #MIN FOR SITE. AS REQ'D UNDER | | | FAC 61G1-16.004. | | | | | | 3)NOTE: PLEASE HAVE ALL CIRCUITING | | | CONFORM TO THE 2002 NEC FOR ARC FAULT | | | PROTECTION. 210.12CIRCUITS#'S 13,15 | | | | | | 4))NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 | | | ALL SD'S ARE REQ'D TO BE WIRED INLINE, | | | HOWEVER, SD'D ARE NOW SHOWN ON SEPARATE | | | CIRCUITS? | | | | | | 5)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND INSERT NEW ONLY. | | | | | | PLANS/PERMIT APPLICATION/COMPUTER WILL | | | NO LONGER REFERENCE MASTER SINCE THE | | | CODE CHANGED 7/1/03 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|