| 2004-01-29 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE PROVIDE ADDRESS ON PLANS | | | AS REQ'D UNDER FAC 61G1-16.004 | | | | | | 2)NOTE: PLEASE SEE NOTES ON PLANS | | | REFERENCE THE 1999 NEC AND THE SFBC | | | WHICH NEITHER ONE IS ANY LONGER IN | | | EFFECT. PLEASE ADJUST PLANS AND ALL | | | CODE #'S TO CORRELATE TO 2002 NEC. | | | | | | 3)NOTE: PLEASE PROVIDE CIRCUITING'S ON | | | PLANS AND PANEL SCHEDULE IN ORDER TO | | | PROVIDE REQ'D ARC FAULT PROTECTION PER | | | THE 2002 NEC. PLANS NOW SHOW WHAT IS | | | REQ'D UNDER THE 1999 NEC. | | | | | | 4)NOTE: PLEASE SEE CODE REFERENCED FOR | | | GROUNDING ELECTRODE SYSTEM. CODES ARE | | | FOR 1999 NEC. PLEASE SEE 2002 | | | | | | 5)NOTE: PLEASE SEE NOTES FROM OTHER | | | REVIEWERS. | | | | | | PLEASE REMOVE ALL OLD/ VOIDED SHEETS | | | AND INSERT NEW SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|