| 2004-02-02 00:00:00 | **************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE 310.15B6 FOR SIZING |
| | OF SEC'S. PLANS MENTION 350A SERVICE AND |
| | 310.15B6 SHOWS 250MCM RATED FOR 300A'S?? |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: PLEASE SEE OCP AND AWG FOR AHU |
| | SHOWN @ 10KW. PLEASE SEE 424.3 FOR MIN |
| | OF 125% FOR OCP. |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | MISSING 2ND FLR, 2' OF WALL SPACE. |
| | |
| | 4)NOTE: PLEASE SEE 210.52E FOR MISSING |
| | RECEPT IN FRONT OF DWELLING. |
| | |
| | 5)NOTE: PANEL SCHEDULE NOW SHOWS ARC |
| | FAULT PROTECTION FOR MAST BEDRM AND |
| | BATH(S). MASTER BEDROOM IS REQ'D BUT NO |
| | OTHER BEDROOMS ARE LISTED?? PLEASE ALSO |
| | NOTE: 210.12 DOES NOT REQUIRE ARC FAULT |
| | PROTECTION FOR BATHS BUT HOWEVER MAY BE |
| | INSTALLED. PLEASE LIST ALL BEDROOMS. |
| | |
| | 6)NOTE: PLEASE SEE AWG AND OCP FOR |
| | DRYER, SHOWN AS 40A AND #8 FOR 5KW.MAX |
| | OCP IS 150% FOR WATER HEATER. |
| | |
| | 7)NOTE: PLEASE SEE ORIG PLANS, REQ'D |
| | TURQUOISE ENG TO PROVIDE CA # ON TITLE |
| | BLOCK AND REQ'D A COMPLETE SIG. NOW |
| | PLANS DO NOT HAVE TITLE BLOCK AT ALL?? |
| | PLEASE SEE THAT THIS COMMENT STILL STAND |
| | -S FOR ALL PLANS AND ALL TRADES, WEATHER |
| | OR NOT COMMENT IS MADE BY OTHER REVIEWER |
| | -S. PLEASE SEE FS 471.023 FOR REQ'D |
| | CA#. PLEASE SEE THAT WE REVIEWED RECORDS |
| | WITH FBPE'S AND HAVE FOUND NO LICENSE |
| | # FOR TURQUOISE ENG. IF INDEED SAID |
| | ENGINEERING FIRM IS LICENSED, THEN |
| | PLEASE PROVIDE ALL LICENSE INFORMATION |
| | ON REQ'D TITLE BLOCK AS REQ'D UNDER |
| | FSAND FAC 61G15-23.002. |
| | IF THERE ARE ANY QUESTIONS ON THIS, |
| | PLEASE CALL. |
| | |
| | 8)NOTE: PLEASE SEE 210.63 FOR RECEPT |
| | REQ'D IN ATTIC FOR AHU. |
| | |
| | 9)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B) ALSO GIVEN BY PLUMB PLAN REVIEW. |
| | |
| | 10)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND INSERT ANY NEW SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND STAMP- |
| | -ING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |