| Date |
Text |
| 2003-12-31 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THAT PLANS SHOW |
| | EXISTING PANEL "A" INSIDE AND NEW/FUTURE |
| | 150A PANEL OUTSIDE. PLEASE SEE THAT PER |
| | 230.72 THIS IS NOT/WILL NOT BE PERMITTED |
| | MAINS ARE REQ'D TO BE GROUPED. |
| | |
| | 2)NOTE: PLEASE ALSO SEE/ NOTE, NO MORE |
| | -THAN 8' OF UNPROETCTED CONDUCTORS ARE |
| | PERMITTED INSIDE HOUSE. 230.70 |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. THERE ARE A FEW MISSING. |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR |
| | MISSING SD INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS AND ON EACH LEVEL OF A |
| | MULTI-LEVEL RESIDENCE. |
| | |
| | 5)NOTE: PLEASE SEE 210.52E FOR MISSING |
| | RECEPTS. |
| | |
| | 6)NOTE:PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12 ON A |
| | SUBMITTED PANEL SCHEDULE. (TO BE SUBMITT |
| | -ED). PLEASE SHOW ALL MIN REQ'D CIRCUITS |
| | , OCP, AWG PER 2002 NEC. |
| | |
| | 7)NOTE: PLEASE SEE THAT WATER HEATER |
| | IS NOT PERMITTED IN CLOTHES CLOSET PER |
| | 422.17. |
| | |
| | 8)NOTE: PLEASE SEE BOTTOM OF LOAD |
| | CALCUALTIONS, SHOWS SERVICE TO BE 150A |
| | AND YET SERVICE IS SHOWN AS POSSIBLE |
| | 350A'S. PLEASE SEE 310.15B6 FOR MIN |
| | SIZE FOR SERVICE ENT CONDUCTORS. |
| | SIZED TO BE MIN 350 MCM. |
| | PLEASE ALSO SEE 250.66 FOR MIN SIZE |
| | OF GROUNDING ELECTRODE CONDUCTOR PER |
| | SEC'S. |
| | |
| | 9)NOTE: PLEASE LIST THE REQ'D DEDICATED |
| | BATH CIRCUITS PER 210.52D/210.11C3 |
| | ON SUBMITTED PANEL SCHEDULE. |
| | |
| | 10)NOTE: PLEASE SEE FAC 61G15-23.002 |
| | FOR LICENSE #'S AND ALL INFORMATION |
| | REQ'D ON TITLE BLOCK. PER FS 471 |
| | PLEASE ALSO NOTE, A COMPLETE SIGNATURE |
| | MUST BE ON PLANS ALSO. INITIALS ARE |
| | NOT ACCEPTABLE PER FBPE'S. |
| | MUST BE SIGNED AS WAS ON LICENSE. |
| | |
| | 11)NOTE: PLEASE SHOW A/C EQUIPMENT ON |
| | PLANS AND REQ'D DISC'S PER 440.11. |
| | PLEASE ALSO SEE 210.70 AND 210.63 FOR |
| | LTS/ RECEPT FOR EQUIPMENT. |
| | |
| | PLEASE SEE THAT ELECTRICAL PLANS HAVE |
| | BEEN VOIDED. PLEASE SUBMIT THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |