Plan Review Notes
Plan Review Notes For Permit 03121023
Permit Number 03121023
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-31 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT PLANS SHOW
 EXISTING PANEL "A" INSIDE AND NEW/FUTURE
 150A PANEL OUTSIDE. PLEASE SEE THAT PER
 230.72 THIS IS NOT/WILL NOT BE PERMITTED
 MAINS ARE REQ'D TO BE GROUPED.
  
 2)NOTE: PLEASE ALSO SEE/ NOTE, NO MORE
 -THAN 8' OF UNPROETCTED CONDUCTORS ARE
 PERMITTED INSIDE HOUSE. 230.70
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. THERE ARE A FEW MISSING.
  
 4)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 MISSING SD INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS AND ON EACH LEVEL OF A
 MULTI-LEVEL RESIDENCE.
  
 5)NOTE: PLEASE SEE 210.52E FOR MISSING
 RECEPTS.
  
 6)NOTE:PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12 ON A
 SUBMITTED PANEL SCHEDULE. (TO BE SUBMITT
 -ED). PLEASE SHOW ALL MIN REQ'D CIRCUITS
 , OCP, AWG PER 2002 NEC.
  
 7)NOTE: PLEASE SEE THAT WATER HEATER
 IS NOT PERMITTED IN CLOTHES CLOSET PER
 422.17.
  
 8)NOTE: PLEASE SEE BOTTOM OF LOAD
 CALCUALTIONS, SHOWS SERVICE TO BE 150A
 AND YET SERVICE IS SHOWN AS POSSIBLE
 350A'S. PLEASE SEE 310.15B6 FOR MIN
 SIZE FOR SERVICE ENT CONDUCTORS.
 SIZED TO BE MIN 350 MCM.
 PLEASE ALSO SEE 250.66 FOR MIN SIZE
 OF GROUNDING ELECTRODE CONDUCTOR PER
 SEC'S.
  
 9)NOTE: PLEASE LIST THE REQ'D DEDICATED
 BATH CIRCUITS PER 210.52D/210.11C3
 ON SUBMITTED PANEL SCHEDULE.
  
 10)NOTE: PLEASE SEE FAC 61G15-23.002
 FOR LICENSE #'S AND ALL INFORMATION
 REQ'D ON TITLE BLOCK. PER FS 471
 PLEASE ALSO NOTE, A COMPLETE SIGNATURE
 MUST BE ON PLANS ALSO. INITIALS ARE
 NOT ACCEPTABLE PER FBPE'S.
 MUST BE SIGNED AS WAS ON LICENSE.
  
 11)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 PLANS AND REQ'D DISC'S PER 440.11.
 PLEASE ALSO SEE 210.70 AND 210.63 FOR
 LTS/ RECEPT FOR EQUIPMENT.
  
 PLEASE SEE THAT ELECTRICAL PLANS HAVE
 BEEN VOIDED. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW