Date Text
2004-02-02 00:00:00DENIED
 1.SHUTTER PRODUCT APPROVALS SUBMITTED
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 2.IMPACT PROTECTION REQUIRED FOR
 SKYLIGHT.PRODUCT APPROVAL DOES NOT
 SPECIFY THAT IT IS IMPACT RESISTANT.
 3.ACCORDING TO THE WEST PALM BEACH
 CODE SEC. 94-546 PROVISIONS FOR FLOOD
 HAZARD REDUCTION.SUBSTANTIAL
 IMPROVEMENTS REQUIRE ENTIRE BUILDING TO
 BE BROUGHT UP TO FLOOD ZONE REQUIREMENTS
 FOR THE CODE.
 CALCULATION OF ALL WORK DONE DURING
 ANY 12 MONTH PERIOD.YOUR STILL OVER
 THE 50% THRESHOLD.
 4.SUBMIT FINISH FLOOR ELEVATATION.
 FINISH FLOOR ELEVATION IN THIS ZONE IS
 7FT. 6IN.