| Date |
Text |
| 2004-02-02 00:00:00 | DENIED |
| | 1.SHUTTER PRODUCT APPROVALS SUBMITTED |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | 2.IMPACT PROTECTION REQUIRED FOR |
| | SKYLIGHT.PRODUCT APPROVAL DOES NOT |
| | SPECIFY THAT IT IS IMPACT RESISTANT. |
| | 3.ACCORDING TO THE WEST PALM BEACH |
| | CODE SEC. 94-546 PROVISIONS FOR FLOOD |
| | HAZARD REDUCTION.SUBSTANTIAL |
| | IMPROVEMENTS REQUIRE ENTIRE BUILDING TO |
| | BE BROUGHT UP TO FLOOD ZONE REQUIREMENTS |
| | FOR THE CODE. |
| | CALCULATION OF ALL WORK DONE DURING |
| | ANY 12 MONTH PERIOD.YOUR STILL OVER |
| | THE 50% THRESHOLD. |
| | 4.SUBMIT FINISH FLOOR ELEVATATION. |
| | FINISH FLOOR ELEVATION IN THIS ZONE IS |
| | 7FT. 6IN. |