| 2003-12-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLA. ADMIN. CODE |
| | FLA. STATUTES |
| | |
| | 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE COMPLIANCE, NOR DOES DOES IT RE- |
| | FLECT THE FLOOR PLAN. SECOND FLOOR MAST- |
| | ER BATH TUB AND SHOWER ARE NOT VENTED. |
| | FLOOR PLAN SHOWS W/C, TUB ON RIGHT SIDE |
| | WITH LAV ON LEFT SIDE FIRST BATH ON THE |
| | FLOOR PLAN, BUT THE RISER SHOWS A LAV |
| | FIRST, WITH A W/C ON THE LEFT SIDE. |
| | THE SECOND BATH SHOWS A LAV, WITH A |
| | SHOWER ON THE RIGHT SIDE AND A W/C ON |
| | THE LEFT SIDE UPSTREAM OF THE FIRST BATH |
| | ROOM, WHEREAS THE RISER DOES NOT SHOW |
| | A LAV AND THE W/C AND SHOWER ARE ON THE |
| | SAME SIDE. PLEASE SUBMIT A RISER DIAGRAM |
| | THAT REFLECTS THE FLOOR PLAN. |
| | 2) IF PRACTICING THROUGH A DULY AUTHROI- |
| | ZED ENGINEERING BUSINESS, ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME AND |
| | LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON |
| | EACH SHEET. 61G15-23.002(2) |
| | 3) THE SIGNATURE OF THE ENGINEER SHALL |
| | BE AFFIXED TO THE SEAL WITH THE DATE. |
| | PER FBPE RULING, INITALS ARE NOT ACCEPT- |
| | ABLE. 61G15-23.002(1) - FS 471.025 |
| | |