Plan Review Notes
Plan Review Notes For Permit 03121023
Permit Number 03121023
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE COMPLIANCE, NOR DOES DOES IT RE-
 FLECT THE FLOOR PLAN. SECOND FLOOR MAST-
 ER BATH TUB AND SHOWER ARE NOT VENTED.
 FLOOR PLAN SHOWS W/C, TUB ON RIGHT SIDE
 WITH LAV ON LEFT SIDE FIRST BATH ON THE
 FLOOR PLAN, BUT THE RISER SHOWS A LAV
 FIRST, WITH A W/C ON THE LEFT SIDE.
 THE SECOND BATH SHOWS A LAV, WITH A
 SHOWER ON THE RIGHT SIDE AND A W/C ON
 THE LEFT SIDE UPSTREAM OF THE FIRST BATH
 ROOM, WHEREAS THE RISER DOES NOT SHOW
 A LAV AND THE W/C AND SHOWER ARE ON THE
 SAME SIDE. PLEASE SUBMIT A RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN.
 2) IF PRACTICING THROUGH A DULY AUTHROI-
 ZED ENGINEERING BUSINESS, ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME AND
 LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. 61G15-23.002(2)
 3) THE SIGNATURE OF THE ENGINEER SHALL
 BE AFFIXED TO THE SEAL WITH THE DATE.
 PER FBPE RULING, INITALS ARE NOT ACCEPT-
 ABLE. 61G15-23.002(1) - FS 471.025
  
 REVIEW BY KEN STEVENS