Plan Review Notes
Plan Review Notes For Permit 03121021
Permit Number 03121021
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-29 00:00:001) NO EXIT SIGNS DIRECTING PERSONS
 TO THE DOOR THAT LEADS TO THE EXISTING
 HC RAMP AND EXIT DOOR.
  
 2) PLEASE EXPLAIN PURPOSE AND FUNCTION
 FOR NEW ROLL UP DOORS.
  
 3) PLEASE PROVIDE DETAILS ON EXISTING
 EXTERIOR STAIR FROM SECOND FLOOR.
 PLEASE INDICATE STAIR RISE AND RUN,
 TREAD SIZE AND HANDRAIL INFORMATION.
  
 4) NO EMERGENCY LIGHTING SHOWN IN
 EXISTING HC RAMP AND EXIT AREA.
  
 5) PLEASE EXPLAIN SINGLE EXIT RATIONALE
 FROM SEVERAL OF THE ROOMS IN SPACE #5.
  
 6) FOR LARGE AREAS OF THE SPACE, THERE
 APPEARS TO BE TOO FEW EMERGENCY
 LIGHT FIXTURES.
  
 7) EXISTING ROLL-UP DOORS APPEAR TO
 REMAIN. PLEASE INDICATE RATING, AND
 WILL THEY BE UP OR DOWN.
  
 8) NO FIRE EQUIPMENT SHOWN ON PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910