| Plan Review Notes For Permit 03121012 |
| Permit Number |
03121012 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-22 00:00:00 | PROVISO: | | | 1. GREASE DUCT SHALL TERMINATE A MINIMUM | | | OF 10 FT FROM PROPERTY LINE, ADJACENT OR | | | CONTINGUOUS BUILDINGS, AND AIR INTAKES. | | | | | | 2. PROVIDE MANUFACTURER SUBMITTAL & | | | INSTALLATION INSTRUCTIONS FOR THE FIRE | | | MASTER 15A ON THE JOBSITE AT THE TIME OF | | | INSPECTION. PLEASE NOTE WELDS TO BE | | | INSPECTED PRIOR TO COVERING WITH FIRE | | | WRAP. | | | | | | 3. SHOULD THE ELEVATION FOR THE FANS | | | EXCEED 16 FT, A PERMANENT MEANS OF | | | ACCESS IS REQUIRED.SLOPEOF THE ROOF | | | GREATER THAN 33% SLOPE SHALL HAVE A | | | LEVEL PLATFORM PER 2001 FBC(M) 306.5 & | | | 306.6. | | | | | | 4.ADDITIONAL PERMIT AND PLANS REQUIRED | | | FOR THE FIRE SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|