| Plan Review Notes For Permit 03120955 |
| Permit Number |
03120955 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2005-06-07 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SMOKE DETECTORS ARE REQUIRED PER | | | 905.2.2 FBC, 8-1.4.1.6.2 NFPA-72. | | | | | | 2} FRONT AND REAR GFI RECEPTACLES ARE | | | REQUIRED PER 210.8(A)(3, 210.52(E). | | | | | | 3} THE DISCONNECTS FOFR THE CONDENSING | | | UNITS MOVED FROM THE REVIEWED PLAN AND | | | ARE NOW IN VIOLATION OF 110.26. | | | | | | 4} MICROWAVE IN LOAD CALCS NOT ON PANEL | | | SCHEDULE. PLEASE CORRELATE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|