2005-06-07 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SMOKE DETECTORS ARE REQUIRED PER
 905.2.2 FBC, 8-1.4.1.6.2 NFPA-72.
  
 2} FRONT AND REAR GFI RECEPTACLES ARE
 REQUIRED PER 210.8(A)(3, 210.52(E).
  
 3} THE DISCONNECTS FOFR THE CONDENSING
 UNITS MOVED FROM THE REVIEWED PLAN AND
 ARE NOW IN VIOLATION OF 110.26.
  
 4} MICROWAVE IN LOAD CALCS NOT ON PANEL
 SCHEDULE. PLEASE CORRELATE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW