Plan Review Notes
Plan Review Notes For Permit 03120955
Permit Number 03120955
Review Stop E
Sequence Number 6
Notes
Date Text
2005-05-11 00:00:00**** REVISIONUNSAT *****
  
 1)NOTE: PLEASE SEE 210.52C1 AND 210.52C3
 FOR MISSING GFI RECEPTS ALONG KITCHEN
 COUNTERSPACE AND PENINSULAR.
 PLEASE ALSO SEE 210.8A6
  
 2)NOTE: PLEASE SEE RECEPTS SHOWN W/IN
 6'IF WET BAR SINK REQUIRED TO BE GFI.
 210.8A3
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT ALONG WALL SPACE. PLEASE SEE IF
 THIS AREA IS CONSIDERED A "HALLWAY" THEN
 RECEPT WILL NOT BE REQUIRED.
  
 4)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND PANEL SCHEDULES.
 PLEASE SEE MICROWAVE SHOWN ON LOAD
 CALCS, BUT NOT ON PANEL SCHEDULE.
 PLEASE SEE LOAD/AMPS FOR FRIG AND
 DISHWASHER BOTH SHOWN AT 19A'S??PLEASE
 SEE MAX LOAD ON A 20A BRANCH CIRCUIT IS
 16A'SHOWEVER THESE DO NOT CORRELATE WITH
 LOAD CALCULATIONS WHICH SHOWS A MUCH
 LESSER LOAD.
 240.24,310.16,210.11 ETC.
  
 5)NOTE: PLEASE SEE CONNECTED AMPS FOR
 DRYER IS SHOWN AT 40A'S, HOWEVER CIRCUIT
 SHOWN IS 30A'S AND KW LOAD ON LOAD
 CALCS, ONLY INDICATE 5KW??
 PLEASE CORRLEATE.
 240,215.5,310.16 ETC.
  
 6 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 7)NOTE: PLEASE VERIFY POOL PUMP MOTOR
 SIZE. PANEL SCHEDULE SHOWS #8AWG, 40A
 OCP FOR 1HP MOTOR??
 PLEASE ALSO CORRELATE WITH LOAD CALCS.
  
 8)NOTE: PLEASE INCLUDE LOAD ON SUB PANEL
 "B". 215.5 220
  
 PLEASE SEE ONE SET OF PLANS HAS ABOVE
 ITEMS REDLINED AT AREAS OF NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]