| 2005-05-11 00:00:00 | **** REVISIONUNSAT ***** |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1 AND 210.52C3 |
| | FOR MISSING GFI RECEPTS ALONG KITCHEN |
| | COUNTERSPACE AND PENINSULAR. |
| | PLEASE ALSO SEE 210.8A6 |
| | |
| | 2)NOTE: PLEASE SEE RECEPTS SHOWN W/IN |
| | 6'IF WET BAR SINK REQUIRED TO BE GFI. |
| | 210.8A3 |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT ALONG WALL SPACE. PLEASE SEE IF |
| | THIS AREA IS CONSIDERED A "HALLWAY" THEN |
| | RECEPT WILL NOT BE REQUIRED. |
| | |
| | 4)NOTE: PLEASE CORRELATE LOAD |
| | CALCULATIONS AND PANEL SCHEDULES. |
| | PLEASE SEE MICROWAVE SHOWN ON LOAD |
| | CALCS, BUT NOT ON PANEL SCHEDULE. |
| | PLEASE SEE LOAD/AMPS FOR FRIG AND |
| | DISHWASHER BOTH SHOWN AT 19A'S??PLEASE |
| | SEE MAX LOAD ON A 20A BRANCH CIRCUIT IS |
| | 16A'SHOWEVER THESE DO NOT CORRELATE WITH |
| | LOAD CALCULATIONS WHICH SHOWS A MUCH |
| | LESSER LOAD. |
| | 240.24,310.16,210.11 ETC. |
| | |
| | 5)NOTE: PLEASE SEE CONNECTED AMPS FOR |
| | DRYER IS SHOWN AT 40A'S, HOWEVER CIRCUIT |
| | SHOWN IS 30A'S AND KW LOAD ON LOAD |
| | CALCS, ONLY INDICATE 5KW?? |
| | PLEASE CORRLEATE. |
| | 240,215.5,310.16 ETC. |
| | |
| | 6 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 7)NOTE: PLEASE VERIFY POOL PUMP MOTOR |
| | SIZE. PANEL SCHEDULE SHOWS #8AWG, 40A |
| | OCP FOR 1HP MOTOR?? |
| | PLEASE ALSO CORRELATE WITH LOAD CALCS. |
| | |
| | 8)NOTE: PLEASE INCLUDE LOAD ON SUB PANEL |
| | "B". 215.5 220 |
| | |
| | PLEASE SEE ONE SET OF PLANS HAS ABOVE |
| | ITEMS REDLINED AT AREAS OF NOTES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |