| 2004-04-21 00:00:00 | *************UNSAT 4TH REVIEW ****** |
| | |
| | 1)NOTE: PLEASE SEE 4X FEE WAS DUE ON |
| | LAST PLAN REVIEW DUE TO THREE REVIEWS |
| | WITH SAME COMMENTS. NOTICE WAS GIVEN IN |
| | NOTES ON 2ND AND 3RD REVIEW FOR THIS |
| | UNDER FS 553.80(2)(B). A COPY OF THE FS |
| | WAS ALSO ATTACHED TO NOTES. |
| | PLEASE SEE BZ #240163 IN THE AMOUNT OF |
| | $4032.00 WAS DUE BEFORE RESUBMITTING |
| | ON 4/20. BZ IS NOW ATTACHED. |
| | PLEASE ALSO SEE NOTES BELOW THAT HAVE |
| | STILL HAVE NOT BEEN ADDRESSED FROM |
| | FIRST 3 REVIEWS AND NOW THE 4TH REVIEW. |
| | PER FS 553.80(2)(B), A 4X FEE IS ACCESS- |
| | ED FOR EACH ONE REVIEW IF ANY OF THE |
| | SAME COMMENTS ARE NOT ADDRESSED FOR CODE |
| | COMPLIANCE. |
| | PLEASE SEE ADDITIONAL BZ ATTACHED FOR |
| | THIS 4XFEE REVIEW.BZ#240164 WHICH MUST |
| | BE PAID BEFORE SUBMITTING PLANS. |
| | PLANS WILL NOT BE PERMITTED TO BE RE- |
| | -SUBBED UNTIL FEES ARE PAID. PER FS. |
| | PLEASE NOTE: IF PLANS COME BACK FOR 5TH |
| | REVIEW AND ANY OF THE SAME COMMENTS FROM |
| | FIRST FOUR REVIEWS ARE NOT ADDRESSED. |
| | WE WILL BE REQ'D TO TURN PLANS INTO |
| | DBPR/ BOARD OF ARCH'S FOR REVIEW PER |
| | BLDG OFFICIAL. |
| | ONE SET OF EACH PLAN IS NOW BEING |
| | RETAINED FOR FILE. |
| | PLEASE SEE COMMENTS BELOW FROM PREVIOUS |
| | REVIEW THAT STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE RISER, STILL SHOWS |
| | AN EQUIPMENT GROUNDING CONDUCTOR BEING |
| | INSTALLED BETWEEN METER AND FIRST MEANS |
| | OF DISCONNECT. PLEASE REMOVE PER 250.6 |
| | 250.24. |
| | |
| | 2)NOTE: PLEASE SEE RECEPT SPACING ON |
| | KITCHEN COUNTERSPACE PER 210.52C1 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 4)NOTE: PLEASE SEE OCP SHOWN FOR OVENS/ |
| | COOKTOP ETC. STILL BEING SHOWN AS 1-POLE |
| | BRKRS. PLEASE SEE OTHER 220V UNITS. |
| | |
| | 5)NOTE:PLEASE SHOW LOAD CALCULATIONS |
| | FOR A RESIDENTIAL DWELLING AS SETFORTH |
| | IN 2002 NEC. 220. 215.5 |
| | |
| | 6)NOTE: PLEASE INCLUDE REQ'D LICENSE # |
| | ON TITLE BLOCK. REQ'D PER FAC 61G1-16.- |
| | 004. PLEASE SEE FS 481.219 FOR REQ'D |
| | CERTIFICATE OF AUTHIRIZATION #. |
| | THIS IS REQ'D |
| | |
| | 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM PER 250.50, SIZE PER 250.66 |
| | |
| | NEW COMMENT: |
| | PLANS HAVE HAD CHANGES TO THEM TO MEET |
| | NEC 210.12.HOWEVER, ALL THESE ARTS |
| | ARE REFERENCING THE FBC? PLEASE CORRECT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. MY # AND E-MAIL ADDRESS |
| | WAS PRINTED AND GIVEN ON PREVIOUS |
| | REVIEWS AS WELL AS BILL TROBAUGH. |
| | AS OF TODAY I HAVE NOT RECEIVED ANY |
| | CALLS FOR ANY QUESTIONS ON THE ABOVE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |