Plan Review Notes
Plan Review Notes For Permit 03120955
Permit Number 03120955
Review Stop E
Sequence Number 4
Notes
Date Text
2004-04-21 00:00:00*************UNSAT 4TH REVIEW ******
  
 1)NOTE: PLEASE SEE 4X FEE WAS DUE ON
 LAST PLAN REVIEW DUE TO THREE REVIEWS
 WITH SAME COMMENTS. NOTICE WAS GIVEN IN
 NOTES ON 2ND AND 3RD REVIEW FOR THIS
 UNDER FS 553.80(2)(B). A COPY OF THE FS
 WAS ALSO ATTACHED TO NOTES.
 PLEASE SEE BZ #240163 IN THE AMOUNT OF
 $4032.00 WAS DUE BEFORE RESUBMITTING
 ON 4/20. BZ IS NOW ATTACHED.
 PLEASE ALSO SEE NOTES BELOW THAT HAVE
 STILL HAVE NOT BEEN ADDRESSED FROM
 FIRST 3 REVIEWS AND NOW THE 4TH REVIEW.
 PER FS 553.80(2)(B), A 4X FEE IS ACCESS-
 ED FOR EACH ONE REVIEW IF ANY OF THE
 SAME COMMENTS ARE NOT ADDRESSED FOR CODE
 COMPLIANCE.
 PLEASE SEE ADDITIONAL BZ ATTACHED FOR
 THIS 4XFEE REVIEW.BZ#240164 WHICH MUST
 BE PAID BEFORE SUBMITTING PLANS.
 PLANS WILL NOT BE PERMITTED TO BE RE-
 -SUBBED UNTIL FEES ARE PAID. PER FS.
 PLEASE NOTE: IF PLANS COME BACK FOR 5TH
 REVIEW AND ANY OF THE SAME COMMENTS FROM
 FIRST FOUR REVIEWS ARE NOT ADDRESSED.
 WE WILL BE REQ'D TO TURN PLANS INTO
 DBPR/ BOARD OF ARCH'S FOR REVIEW PER
 BLDG OFFICIAL.
 ONE SET OF EACH PLAN IS NOW BEING
 RETAINED FOR FILE.
 PLEASE SEE COMMENTS BELOW FROM PREVIOUS
 REVIEW THAT STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE RISER, STILL SHOWS
 AN EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METER AND FIRST MEANS
 OF DISCONNECT. PLEASE REMOVE PER 250.6
 250.24.
  
 2)NOTE: PLEASE SEE RECEPT SPACING ON
 KITCHEN COUNTERSPACE PER 210.52C1
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE SEE OCP SHOWN FOR OVENS/
 COOKTOP ETC. STILL BEING SHOWN AS 1-POLE
 BRKRS. PLEASE SEE OTHER 220V UNITS.
  
 5)NOTE:PLEASE SHOW LOAD CALCULATIONS
 FOR A RESIDENTIAL DWELLING AS SETFORTH
 IN 2002 NEC. 220. 215.5
  
 6)NOTE: PLEASE INCLUDE REQ'D LICENSE #
 ON TITLE BLOCK. REQ'D PER FAC 61G1-16.-
 004. PLEASE SEE FS 481.219 FOR REQ'D
 CERTIFICATE OF AUTHIRIZATION #.
 THIS IS REQ'D
  
 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50, SIZE PER 250.66
  
 NEW COMMENT:
 PLANS HAVE HAD CHANGES TO THEM TO MEET
 NEC 210.12.HOWEVER, ALL THESE ARTS
 ARE REFERENCING THE FBC? PLEASE CORRECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. MY # AND E-MAIL ADDRESS
 WAS PRINTED AND GIVEN ON PREVIOUS
 REVIEWS AS WELL AS BILL TROBAUGH.
 AS OF TODAY I HAVE NOT RECEIVED ANY
 CALLS FOR ANY QUESTIONS ON THE ABOVE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]