 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.ALSO NOTE THAT THESE COMMENTS
 ARE FROM THE FIRST TWO REVIEWS AND WERE
 NOT ADDRESSED. THE DESIGN PROFESSIONAL
 IS THEREFORE RESPONSIBLE FOR THE FEES
 IMPOSSED UNDER FS. 553.80(2)(B),
 ATTACHED.
  
 1} THE EQUIPMENT GROUNDING CONDUCTOR IN
 THE FEEDER TO THE FIRST MEANS OF
 DISCONNECT IS IN VIOLATION OF 250.24 &
 250.6.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT PER110.9,110.10 & 215.5.
  
 3} THERE ARE STILL RECEPTACLES MISSING
 FROM THE KITCHEN COUNTERTOPS PER
 210.52(C)(1).
  
 4} NOTE #9 INDICATES MINIMUM WIRE SIZE
 @ #12 AWG, THE PANEL SCHEDULES LISTS #14
 BEING USED ON SEVERAL CIRCUITS. PLEASE
 CORRELATE.
  
 5} THERE IS NO RECEPTACLE AT THE FRONT
 OF THE RESIDENCE, VIOLATION OF
 210.52(E).
  
 6} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250.50 ALL THAT APPLY,
 INCLUDE BUILDING STEEL.
  
 7} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN, INCLUDING METER
 AND MAIN DISCONNECT.
  
 8} VERIFY THE OCP FOR THE COOKTOP AND
 WALL OVEN. SEE NOTE #9, COMMENTS.
  
 9} SHOW LOADS IN CALCLATION PER ARTICLE
 220 NEC. INDICATE METHOD (ARTICLE) USED.
  
 10} RECEPTACLES ARE STILL MISSING IN THE
 BREAKFAST ROOM AND BEDROOM #3 IN
 VIOLATION OF 210.52(A)(2).
  
 11} THERE ARE 2 ROOMS DESIGNATED BEDROOM
 #3. PLEASE CORRELATE WITH ARCHITECTURAL
 PLANS.
  
 12} THE RECEPTALE IN THE BAR MUST BE GFI
 PROTECTED PER 210.8(A)(7).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026