| Date |
Text |
| 2004-04-08 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW.ALSO NOTE THAT THESE COMMENTS |
| | ARE FROM THE FIRST TWO REVIEWS AND WERE |
| | NOT ADDRESSED. THE DESIGN PROFESSIONAL |
| | IS THEREFORE RESPONSIBLE FOR THE FEES |
| | IMPOSSED UNDER FS. 553.80(2)(B), |
| | ATTACHED. |
| | |
| | 1} THE EQUIPMENT GROUNDING CONDUCTOR IN |
| | THE FEEDER TO THE FIRST MEANS OF |
| | DISCONNECT IS IN VIOLATION OF 250.24 & |
| | 250.6. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT PER110.9,110.10 & 215.5. |
| | |
| | 3} THERE ARE STILL RECEPTACLES MISSING |
| | FROM THE KITCHEN COUNTERTOPS PER |
| | 210.52(C)(1). |
| | |
| | 4} NOTE #9 INDICATES MINIMUM WIRE SIZE |
| | @ #12 AWG, THE PANEL SCHEDULES LISTS #14 |
| | BEING USED ON SEVERAL CIRCUITS. PLEASE |
| | CORRELATE. |
| | |
| | 5} THERE IS NO RECEPTACLE AT THE FRONT |
| | OF THE RESIDENCE, VIOLATION OF |
| | 210.52(E). |
| | |
| | 6} THE GROUNDING ELECTRODE SYSTEM MUST |
| | COMPLY WITH 250.50 ALL THAT APPLY, |
| | INCLUDE BUILDING STEEL. |
| | |
| | 7} SHOW THE LOCATION OF THE SERVICE |
| | EQUIPMENT ON THE PLAN, INCLUDING METER |
| | AND MAIN DISCONNECT. |
| | |
| | 8} VERIFY THE OCP FOR THE COOKTOP AND |
| | WALL OVEN. SEE NOTE #9, COMMENTS. |
| | |
| | 9} SHOW LOADS IN CALCLATION PER ARTICLE |
| | 220 NEC. INDICATE METHOD (ARTICLE) USED. |
| | |
| | 10} RECEPTACLES ARE STILL MISSING IN THE |
| | BREAKFAST ROOM AND BEDROOM #3 IN |
| | VIOLATION OF 210.52(A)(2). |
| | |
| | 11} THERE ARE 2 ROOMS DESIGNATED BEDROOM |
| | #3. PLEASE CORRELATE WITH ARCHITECTURAL |
| | PLANS. |
| | |
| | 12} THE RECEPTALE IN THE BAR MUST BE GFI |
| | PROTECTED PER 210.8(A)(7). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |