| 2003-12-30 00:00:00 | ************ UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THAT AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS NOT INSTALLED |
| | BETWEEN METER AND FIRST MEANS OF DISC. |
| | 250.24. PLEASE REMOVE. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATING FOR ALL |
| | SERVICE EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS AND BRKRS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FUALT CURRENT. |
| | PER 110.9/ 215.5 |
| | IT IS NOTED THAT AIC RATING IS NOTED |
| | FOR BRANCH BRKRS IN PANELS. |
| | |
| | 3)NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | KITCHEN COUNTERSPACE PER 210.52C1 |
| | |
| | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | WITH MIN LOADS REQ'D AS SETFORTH IN ART |
| | 220 OF THE NEC. |
| | |
| | 5)NOTE: PLEASE SEE NOTE #9, MENTIONS |
| | MIN AWG TO BE #12, PANEL SCHEDULE DOES |
| | NOT CORRELATE WITH THIS. PLEASE |
| | CORRELATE. |
| | |
| | 6)NOTE: PLEASE LIST ALL THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS PER 210.12 |
| | 2002 NEC. |
| | |
| | 7)NOTE: PLEASE CORRELATE FEEDERS FOR |
| | SUB PANEL 'B'. RISER SHOWS #3/0'S AND |
| | PANEL "A" SHOWS #3. |
| | |
| | 8)NOTE: PLEASE SEE 210.52E FOR FRONT |
| | AND REAR RECEPTS. MISSING FRONT. |
| | |
| | 9)NOTE: PLEASE INCLUDE FOOTER STEEL, |
| | COLD WATER PER 250.50 ON RISER DIAGRAM |
| | FOR GROUNDING ELECTRODE SYSTEM. |
| | |
| | 10)NOTE: PLEASE SEE MISSING RECEPT ON |
| | 2' OF WALL MASTER BR. 210.52 |
| | |
| | 11)NOTE: PLEASE SHOW SERVICE ON PLANS/ |
| | LOCATION OF METER AND MAIN. |
| | |
| | 12)NOTE: PLEASE VERIFY OCP FOR BOTH |
| | COOKTOP AND WALL OVEN. SHOWN AS 60A?? |
| | PLEASE SEE THAT THIS IS NOT A COMMON |
| | SIZE, PLEASE VERIFY. |
| | |
| | 13)NOTE: PLEASE SEE 220.16B FOR MIN KVA |
| | OF WASHER/LAUNDRY CIRCUIT. SHOWN WITH |
| | LOAD @ 10A'S??. PLEASE SEE NOTE #4 |
| | |
| | 14)NOTE: PLEASE SEE MISSING RECEPTS |
| | IN BR#3 AND BRKFST AREA PER 210.52 |
| | PLEASE ALSO SEE RECEPT SPACING IN DINING |
| | RM AND ANY OTHER AREAS. DINING RM HAS |
| | RECEPT IN CENTER OF DOORWAY (MISPRINT). |
| | |
| | 15)NOTE: PLEASE SEE THAT THERE ARE TWO |
| | ROOMS SHOWN AS BEDROOM #3. PLEASE ADJUST |
| | |
| | 16)NOTE: PLEASE SEE 210.8 FOR GFI |
| | PROETCTION REQ'D IN BAR AREA. LOCAL |
| | AMENDMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |