Plan Review Notes
Plan Review Notes For Permit 03120955
Permit Number 03120955
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-20 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT. CITY AMENDMENTS TO FBC
 1804.2.2.
  
 4) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED WITHIN 3 FEET OF THE PROPERTY
 LINE PER FBC TABLE 600. SPECIFY THIS ON
 THE PLANS.
  
 5) GLASS BLOCK WITHIN THREE FEET OF A
 TUB OR SHOWER ARE REQUIRED TO HAVE A
 MINIMUM UNIFORM FACE THICKNESS OF 0.25"
 PER FBC 2405.2. SPECIFY ON THE PLANS.
  
 6) WINDOWS WITHIN THREE FEET OF A TUB OR
 SHOWER ARE REQUIRED TO HAVE SAFETY
 GLAZING PER FBC 2405.2. SPECIFY ON PLANS
 THAT THE WINDOWS IN MASTER BATH ARE
 TEMPERED.
  
 7) SPECIFY THE SIZE OF THE GLASS BLOCK
 OPENINGS.
  
 8) SPECIFY THE TYPE AND SIZES OF THE
 EGRESS WINDOWS IN THE GUEST BEDROOM.
  
 9) INDICATE THE SIZES OF ALL OF THE
 TRANSOM AND FIXED GLASS WINDOWS.
  
 10) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS. SEE FBC 2309.6.
  
 11) PROVIDE AT LEAST ONE FULL BATH WITH
 A DOOR THAT HAS A 29" CLEAR OPENING AS
 REQUIRED BY FBC CHAPTER 11.
  
 12) SUBMIT MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE GAS BBQ.
  
 13) THE FOOT PRINT OF THE STRUCTURE ON
 THE SURVEY DOES NOT MATCH THE PLANS.
 SUBMIT CORRECTED SURVEY.
  
 14) THE ROOF SHEATHING IS REQUIRED TO BE
 NAILED AT 4"OC AT THE EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 PER CITY AMEND.
 TO FBC TABLE 2306.1. THE CORNERS OF HIP
 ROOFS ARE ZONE 3. PLEASE REVISE THE NOTE
 ON A6.
  
 15) SPECIFY THE FOUNDATION FOR THE 5'
 WALL AT THE GARDEN COURT ON S1.
  
 16) PROVIDE DETAILS OF THE CUSTOM WALL
 BRACKETS SPECIFIED IN THE CONNECTOR
 SCHEDULE ON S3.
  
 17)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASEIN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23. REVISE THE CONNECTOR
 SCHEDULE ON S3 ACCORDINGLY. SEE NOTES ON
 THE PLAN.
  
 18) UPDATE THE USP HC 10/10-2 WHICH ARE
 NO LONGER LISTED IN THE USP CATALOG.
  
 19) SPECIFY THE WELD TYPES AND UPLIFT
 CAPACITIES FOR THE STEEL COLUMNS ON S4.
  
 20) CORRECT THE HEIGHT AND EXPOSURE
 COEFFICIENT VALUES IN TABLE 1606.2D ON
 S4. SEE MARKS ON THE PLAN.
  
 21) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - ONE HOUR FIRE RATED GLASS BLOCK
 - SINGLE HUNG WINDOWS
 - FIXED GLASS WINDOWS
 - ARCHED TOP WINDOWS
 - MULLIONS
 - OVERHEAD GARAGE DOORS
 - DOUBLE INSWING ENTRY DOORS
 - PANEL DOORS
 - SLIDING GLASS DOORS
 - TRUSS CONNECTORS
 - STORM PANELS
  
 22) IN ADDITION TO THE PRODUCT APPROVALS
 FOR THE STORM PANELS, SUBMIT KEY PLANS
 AND AN INSTALLATION SCHEDULE. SPECIFY
 THE MOUNT TYPE AND FASTNER TYPE &
 SPACINGS THAT WILL BE USED. THIS INFO
 IS REQUIRED PRIOR TO ISSUANCE OF THIS
 PERMIT OR A SEPARATE PERMIT AND FEES
 WILL BE REQUIRED.
  
 NOTE: NO BUTT GLASS OR STOREFRONTS ARE
 INDICATED ON THE PLANS. PLEASE REMOVE
 THESE PRODUCT APPROVALS FORM SUBMITTAL.
  
 23) THERE WAS NO ROOFING CONTRACTOR
 SIGNED ON THE PERMIT APPLICATION WHEN IT
 WAS SUBMITTED. THEREFORE, A SEPARATE
 PERMIT AND FEES WILL BE REQUIRED.
 PRODUCT APPROVALS WILL BE REQUIRED AT
 THAT TIME. PLEASE REMOVE THE PRODUCT
 APPROVALS FOR THE ROOF TILES FROM THIS
 SUBMITTAL.
  
 IN ORDER TO AID PLAN REVIEW TIME, PLEASE
 SUBMIT OLD PLAN SHEETS THAT HAVE BEEN
 REMOVED AND REPLACED BY REVISED SHEETS.
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714